Mercury Lithium Battery User Manual
Mercury Lithium Battery User Manual

Mercury Lithium Battery User Manual: 24V/48V LiFePO4 Series

About This Manual

This manual covers the Mercury 24V and 48V LiFePO4 lithium battery series: the 25.6V 200Ah 5kWh, 51.2V 100Ah 5kWh, 51.2V 200Ah 10kWh and 51.2V 300Ah 15kWh packs. Read it carefully before you install or use the battery, and follow its instructions during installation. If anything is unclear, contact Mercury Direct on 07037451701 for clarification before you proceed. Scan the QR codes on the printed cover to download the WiFi app and the app installation guide.

Contents

1. Introduction

The 24V/48VDC series lithium battery power bank is a new energy storage product developed to supply reliable power to various types of equipment and systems. It is especially suitable for applications with high power, limited installation space, restricted load-bearing and a long cycle life requirement.

The series has a built-in BMS (battery management system) which manages and monitors cell information including voltage, current and temperature. The BMS also balances cell charging and discharging to extend cycle life.

Multiple batteries can be connected in parallel to expand capacity and power, for larger capacity and longer power-supply duration requirements.

The battery must be rated above the inverter it will be connected to. In practice that means three checks. The battery voltage must match the inverter battery voltage: the Mercury 25.6V pack for 24V inverters and the Mercury 51.2V packs for 48V inverters. The battery’s maximum discharge current in section 2.2 must be equal to or higher than the current the inverter draws at full load, and its maximum charge current must be equal to or higher than the combined charging current from all sources (solar and grid or generator charging together). For example, the Mercury 25.6V 200Ah pack’s 150 A maximum discharge at its 24.0 V cut-off gives 3,600 W at the battery, before inverter losses. And the battery’s kWh capacity should cover the hours of backup the customer needs. Mercury Direct checks all three before confirming any Mercury inverter and battery pairing; call 07037451701.

Mercury Direct lithium battery overview: 24V and 48V LiFePO4 battery components
LCD displayMERCURY LITHIUM BATTERY
BreakerSwitch
  • 1LCD display for battery status and data.
  • 2Circuit breaker for the battery output.
  • 3 to 5RS485 parallel ports, RS485/CAN communication port and DIP address switches.
  • 6 to 9Power switch, remote WiFi antenna, and positive and negative battery terminals.

This simplified product diagram identifies the main parts described in the Mercury 24V/48V lithium battery manual. See section 2.3 for the full numbered interface definitions.

1.1 Safety Reminders

  • 1) It is very important and necessary to read the user manual carefully (included in the accessories) before installing or using the battery. Failure to do so, or to follow any of the instructions or warnings in this document, can result in electrical shock, serious injury or death, or can damage the battery and potentially render it inoperable.
  • 2) If the battery is stored for a long time, it must be charged every six months, and the state of charge should be no less than 90%.
  • 3) The battery must be recharged within 12 hours after being fully discharged.
  • 4) Do not expose the cable outside.
  • 5) All battery terminals must be disconnected for maintenance.
  • 6) Contact Mercury Direct on 07037451701 within 24 hours if anything abnormal occurs.
  • 7) Do not use cleaning solvents to clean the battery.
  • 8) Do not expose the battery to flammable or harsh chemicals or vapours.
  • 9) Do not paint any part of the battery, including any internal or external components.
  • 10) Do not connect the battery to PV solar wiring directly.
  • 11) Warranty claims are excluded for direct or indirect damage caused by the items above.
  • 12) Do not insert any foreign object into any part of the battery.

1.2 Warning: Before Connecting

  • 1) After unpacking, check the product against the packing list first. If the product is damaged or parts are missing, contact Mercury Direct on 07037451701.
  • 2) Before installation, cut off the grid power and make sure the battery is in the switched-off state.
  • 3) Wiring must be correct. Do not mistake the positive and negative cables, and ensure there is no short circuit with the external device.
  • 4) It is prohibited to connect the battery to AC power directly.
  • 5) The battery has an embedded BMS. The wall-mounted cases are not allowed to be used in series. In the communication state, a maximum of 16 parallel connections is allowed.
  • 6) The battery system must be well grounded, and the ground resistance must be less than 1Ω.
  • 7) Make sure the electrical parameters of the battery system are compatible with the related equipment.
  • 8) Keep the battery away from water and fire.

1.3 Warning: In Use

  • 1) If the battery system needs to be moved or repaired, the power must be cut off and the battery completely shut down.
  • 2) It is prohibited to connect the battery with a different type of battery.
  • 3) It is prohibited to operate the battery with a faulty or incompatible inverter.
  • 4) It is prohibited to disassemble the battery (QC tab removed or damaged).
  • 5) In case of fire, only a dry powder fire extinguisher may be used. Liquid fire extinguishers are prohibited.
  • 6) Do not open, repair or disassemble the battery; only manufacturer staff may do so. The manufacturer does not accept any consequences or related responsibility arising from violation of safe operation or from violation of design, production and equipment safety standards.

2. Features and Specifications

2.1 Features

  • Environmental: The manufacturer describes the module as non-toxic, non-polluting and environmentally friendly in normal use. A damaged or leaking pack must still be treated as hazardous; see section 6.
  • LiFePO4 cathode: The cathode material is lithium iron phosphate, with high safety performance and long cycle life.
  • BMS protection: The battery management system protects against over-discharge, over-charge, over-current and high or low temperature.
  • Automatic balancing: The system automatically manages the charge and discharge state and balances the current and voltage of each cell.
  • Flexible configuration: Multiple battery modules can be connected in parallel to expand capacity and power.
  • Low noise: A self-cooling design reduces the noise of the whole system.
  • Low self-discharge: The module can sit for up to six months on the shelf without charging. It has no memory effect and performs well under shallow charge and discharge.
  • Working temperature: Minus 10°C to 50°C (charge 0°C to 50°C, discharge minus 10°C to 50°C), with excellent discharge performance and cycle life.

2.2 Specifications

Mercury lithium battery specifications by model (24V and 48V series)
Basic parameters25.6V 100Ah25.6V 200Ah25.6V 300Ah51.2V 100Ah51.2V 200Ah51.2V 300Ah51.2V 350Ah
Nominal capacity2,560Wh5,120Wh7,680Wh5,120Wh10,240Wh15,360Wh17,920Wh
Fast charge voltage28.8Vdc28.8Vdc28.8Vdc57.6Vdc57.6Vdc57.6Vdc57.6Vdc
Float charge voltage28.0Vdc28.0Vdc28.0Vdc56.0Vdc56.0Vdc56.0Vdc56.0Vdc
Low DC cut-off voltage24.0Vdc24.0Vdc24.0Vdc48.0Vdc48.0Vdc48.0Vdc48.0Vdc
Max. charge current50A100A150A50A100A150A175A
Max. discharge current100A150A200A100A150A200A200A
Peak discharge current (1 sec)150A225A300A150A225A300A300A
Mercury lithium battery common specifications
ParameterAll models
DisplayLED status indicator, LCD display
CommunicationRS485, CAN
Working temperatureCharge 0°C to 50°C; discharge minus 10°C to 50°C
Shelf temperatureMinus 10°C to 50°C
CertificationUN38.3, MSDS

Mercury currently stocks four models from this table: the Mercury Lithium LiFePO4 25.6V 200Ah 5kWh, the Mercury Lithium LiFePO4 51.2V 100Ah 5kWh, the Mercury Lithium LiFePO4 51.2V 200Ah 10kWh and the Mercury Lithium LiFePO4 51.2V 300Ah 15kWh. The 25.6V pack pairs with 24V inverters and the 51.2V packs with 48V inverters. Current prices are on each product page and in the Mercury lithium battery category.

2.3 Equipment Interface Instruction

Mercury 24V/48V LiFePO4 battery interface diagram: LCD, circuit breaker, communication ports and terminals

Front view

1 · LCD displayMERCURY LITHIUM BATTERY
Side panel

Side interface callouts

  1. 2Circuit breaker: battery output circuit breaker.
  2. 3Battery RS485 interfaces: parallel battery or upper-computer communication.
  3. 4RS485/CAN interface: communication between the BMS and inverter.
  4. 5Device address: DIP switches for each BMS protection board.
  5. 6Power switch: ON enables battery output; OFF removes output voltage.
  6. 7Remote WiFi external antenna.
  7. 8Positive battery terminal: red is positive.
  8. 9Negative battery terminal: black is negative.

Callout 1 is the LCD on the front. Callouts 2 to 9 identify the circuit breaker, RS485 and CAN communication ports, DIP address switches, power switch, WiFi antenna, and battery terminals.

Mercury lithium battery equipment interfaces
No.InterfaceFunction
1LCD displayDisplays the working status data pages.
2Circuit breakerThe battery output circuit breaker.
3Battery RS485 interfacesRS485 protocol for communication between multiple parallel batteries, or with upper-computer software, at baud rate 19200.
4RS485/CAN interfaceRS485/CAN protocol between the BMS controller and the inverter for output of battery information, or with upper-computer software, at baud rate 9600.
5Device addressDIP switches used to set the address of each BMS protection board.
6Power switchON: the battery is turned on and has output voltage. OFF: the battery is turned off and has no output voltage.
7Remote WiFi external antennaAntenna for the remote WiFi module.
8Positive battery terminalOne pair of terminals; red is the battery positive pole.
9Negative battery terminalOne pair of terminals; black is the battery negative pole.

Setting DIP Switch Addresses for Multiple Batteries in Parallel

Each battery in a parallel group needs its own address. Set the four DIP switches on each pack as shown. Address 1 is the host (master) pack that communicates with the inverter; addresses 2 to 15 are slave packs.

Mercury lithium battery DIP switch address diagram for parallel packs

Address 1 · host pack

1
ON
2
OFF
3
OFF
4
OFF

The host (master) battery communicates with the inverter.

Address 2 · slave pack

1
OFF
2
ON
3
OFF
4
OFF

The slave battery links to the host through the parallel RS485 ports.

These two examples show the first parallel-pack addresses. Use the table below for the DIP switch settings for addresses 0 to 15.

Mercury lithium battery DIP switch addresses for parallel packs
Switch 1Switch 2Switch 3Switch 4AddressInstruction
OFFOFFOFFOFF0Automatic address coding
ONOFFOFFOFF1Pack 1, host (master) unit
OFFONOFFOFF2Pack 2, slave unit
ONONOFFOFF3Pack 3, slave unit
OFFOFFONOFF4Pack 4, slave unit
ONOFFONOFF5Pack 5, slave unit
OFFONONOFF6Pack 6, slave unit
ONONONOFF7Pack 7, slave unit
OFFOFFOFFON8Pack 8, slave unit
ONOFFOFFON9Pack 9, slave unit
OFFONOFFON10Pack 10, slave unit
ONONOFFON11Pack 11, slave unit
OFFOFFONON12Pack 12, slave unit
ONOFFONON13Pack 13, slave unit
OFFONONON14Pack 14, slave unit
ONONONON15Pack 15, slave unit

Note on pack count (Mercury Direct): the manual allows up to 16 packs in parallel in the communication state, while its DIP table assigns manual addresses 1 to 15, with address 0 reserved for automatic address coding. For a system of more than 15 packs, contact Mercury Direct on 07037451701 so the addressing can be confirmed with the manufacturer before installation.

Communication Interface Pin Definition

All communication ports are RJ45 sockets. As drawn in the manual, looking into the battery’s RJ45 socket with the latch slot at the top, the pins are numbered 8 to 1 from left to right.

Mercury lithium battery RJ45 communication pinout diagram, looking into the battery socket with the latch slot at the top

Read each port from left to right as pins 8, 7, 6, 5, 4, 3, 2 and 1. On a phone, swipe each pin row sideways to see all eight pins. Signal labels for the inverter RS485/CAN port and battery parallel RS485 ports are shown below.

Inverter RS485/CAN port

8RS485-B1
7RS485-A1
6GND
5CANL
4CANH
3GND
2RS485-A1
1RS485-B1

Battery parallel RS485 ports

8RS485-B
7RS485-A
6GND
5NC
4NC
3Addr-IN / Addr-OUT
2RS485-A
1RS485-B

NC means no connection. The following tables provide the full pin definition for each port.

Mercury lithium battery inverter RS485/CAN port pin definition
RJ45 pinInverter RS485/CAN port
1, 8RS485-B1
2, 7RS485-A1
3, 6GND
4CANH
5CANL
Mercury lithium battery parallel RS485 port pin definition
RJ45 pinBattery parallel RS485 port (IN)Battery parallel RS485 port (OUT)
1, 8RS485-BRS485-B
2, 7RS485-ARS485-A
3Addr-INAddr-OUT
4, 5NCNC
6GNDGND

2.4 LCD Display Instruction

Mercury lithium battery LCD home screen and slave battery data fields

Home screen · battery status

  • 1State of charge (SOC) and pack voltage.
  • 2Battery current, power and charge or discharge state.
  • 3Number of battery packs communicating in parallel.
  • 4Minimum and maximum cell voltage, in millivolts, and battery temperature.

Slave page · individual pack data

  • 1 to 8Select a pack number to view that battery’s data.
  • V/APack voltage and current.
  • MOSCharge and discharge MOS status.
  • T1 to T4Four temperature sensor readings and the individual cell voltages (sixteen on the Mercury 51.2V models).

The LCD home page summarizes the communicating Mercury lithium battery system. The slave page displays detailed status for the selected parallel pack.

2.4.1 Home and slave pages. The first screen shows state of charge, pack voltage, current, the number of packs in parallel, power, charge or discharge state, and the minimum and maximum cell voltage and temperature. Tap the slave page icon to view the parallel packs; when multiple battery packs are communicating in parallel, tap a pack number to view that pack’s data, including its individual cell voltages (sixteen on the Mercury 51.2V models, as shown in the manual’s screen) and the T1 to T4 temperature sensors.

Mercury lithium battery installer login and inverter communication settings

Installer login

Installer access required

Password field intentionally omitted. Mercury Direct provides the installer password to authorised technicians.

Inverter communication parameter page

CAN protocolSelect the protocol that matches the inverter · Write
RS485 protocolSelect the protocol that matches the inverter · Write
Charge voltage/currentSet within the limits in section 2.2 · Write
Discharge voltage/currentSet within the limits in section 2.2 · Write

These are installer settings. Only a trained installer should change communication protocols or charge and discharge limits.

2.4.2 Login and inverter communication parameters. Tap the login icon to open the login page and enter the installer password to log in. Because this page controls the battery’s charge and discharge limits, the password is issued to installers by Mercury Direct on 07037451701 and is not published here. Then tap the parameter icon to open the inverter communication parameter page. Here the installer selects the CAN protocol and the RS485 protocol to match the inverter, and can write the charge voltage, charge current, discharge voltage and discharge current limits. These settings should only be changed by the installer, and must stay within the values in section 2.2.

Mercury lithium battery LCD setup page: backlight sleep delay and language options
LCD backlight sleep delay

Default delay: 30 seconds.

Use Read to view the setting and Write to save a change.

Display languages

Chinese · English · Arabic

Tap a language option to select it.

2.4.3 Setup page. Tap the setup icon to open the setup page. Here you can set the LCD backlight sleep delay time (default 30 seconds) with the Read and Write buttons, and tap a language icon to choose Chinese, English or Arabic.

3. Safe Handling of Lithium Battery Guide

Installer Only

Wiring, paralleling batteries, setting DIP addresses, disconnecting DC cables and measuring live circuits must be done by a trained installer. Contact Mercury Direct on 07037451701 to arrange installation and commissioning.

3.1 Schematic Diagram of Solution

Mercury lithium battery system diagram: solar PV array, public grid, inverter, battery module and local load
Solar PV array

DC solar input

→
Inverter

PV and grid input

Public grid

AC grid supply

→
Inverter

Manages the system connection

Mercury lithium battery module

Battery storage

↔
Inverter

Battery connection

Inverter

System output

→
Local load

Appliances and equipment

Connection path in this arrangement: solar PV array and public grid feed the inverter; the Mercury lithium battery connects to the inverter; the inverter supplies the local load. Charging may also come through an MPPT charge controller, but never connect raw solar panel output, AC mains or the load directly to the battery.

In the arrangement shown, the battery module connects to the inverter. The PV array and the public grid both feed the inverter, and the inverter supplies the local load. The battery never connects directly to the PV array, the grid or the load.

3.2 Tools

Tools required to install a Mercury lithium battery
ToolUsed for
Wire cutterCutting the DC power cables to length
Crimping modular plierCrimping RJ45 communication connectors
ScrewdriverTerminal screws and the wall-mounting brackets
Tools for Mercury lithium battery installation: wire cutter, crimping modular plier and screwdriver
Wire cutter

Cut DC power cables to the required length.

Crimping modular plier

Crimp RJ45 communication connectors.

Screwdriver

Work on terminal screws and wall-mounting brackets.

Use properly insulated tools to reduce the risk of accidental electric shock or short circuits.

Note: use properly insulated tools only, to prevent accidental electric shock or short circuits.

3.3 Safety Gear

It is recommended to wear the following safety gear when working with the battery pack:

Safety gear for working on a Mercury lithium battery
Safety gearProtects against
Insulated glovesElectric shock and short circuits at the terminals
Safety gogglesSparks and electrolyte splash
Safety shoesDropped equipment during wall mounting
Safety gear for Mercury lithium battery installation and handling
Insulated gloves

Help protect against electric shock and terminal short circuits.

Safety goggles

Help protect the eyes from sparks and electrolyte splash.

Safety shoes

Help protect against dropped equipment during wall mounting.

4. Installation

Installer Only

Wiring, paralleling batteries, setting DIP addresses, disconnecting DC cables and measuring live circuits must be done by a trained installer. Contact Mercury Direct on 07037451701 to arrange installation and commissioning.

4.1 One Battery Connected to an Inverter

Mercury lithium battery single-pack wiring diagram: address 1 communication link to inverter
Mercury lithium battery

DIP address 1 · positive and negative battery terminals

Inverter

CAN/485 communication port and battery input

Communication link (dashed)Power connection (solid)
Communication: battery RS485/CAN interface to inverter CAN/485 port using the communication cable.
DC positive: battery positive terminal to inverter battery positive.
DC negative: battery negative terminal to inverter battery negative.

Battery wiring and communication connections are installer work. Confirm inverter compatibility and polarity before commissioning.

Set the battery to address 1. Connect the battery’s RS485/CAN interface (item 4 in section 2.3) to the inverter’s CAN/485 port with the supplied communication cable, and connect the power cables from the battery terminals to the inverter’s battery input, positive to positive and negative to negative.

4.2 Multiple Batteries Connected to an Inverter

Mercury lithium battery parallel wiring diagram: address 2 and address 1 packs connected to an inverter
Battery pack · address 2

Slave pack · parallel RS485 port

Battery pack · address 1

Host pack · parallel RS485 and inverter CAN/485 links

Inverter

Connect communication cable to address 1 only

Communication link (dashed)Power connection (solid)
Parallel communication: link battery packs through their RS485 parallel ports using parallel communication cables.
Parallel power: connect every battery positive terminal to the positive bus and every negative terminal to the negative bus.

Use unique DIP addresses. Address 1 is the host pack. Connect Mercury battery packs in parallel only; never connect them in series.

Set the battery nearest the inverter to address 1 and each additional battery to the next address (2, 3 and so on, up to the maximum of 16 packs in parallel). The DIP table covers addresses 1 to 15; for more than 15 packs, contact Mercury Direct on 07037451701 to confirm the addressing with the manufacturer before installation. Link the packs through their battery parallel RS485 ports (item 3 in section 2.3) using the parallel communication cables, and connect only the address 1 pack to the inverter’s CAN/485 port. Connect all power cables in parallel: every positive terminal to the positive bus and every negative terminal to the negative bus. Never connect packs in series.

4.3 Installation Location

Make sure that the installation location meets the following conditions:

Installation location requirements for a Mercury lithium battery
ConditionRequirement
WaterThe area is completely waterproof
FloorFlat and level
HazardsNo flammable or explosive materials
Ambient temperature0°C to 50°C
StabilityTemperature and humidity maintained at a constant level
DustMinimal dust and dirt
MountingFitting screws used to fix the box to the wall (wall-mount models). Heavier models may be supplied as floor-standing cabinets; confirm the mounting format for your model with Mercury Direct on 07037451701
Mercury lithium battery wall mounting diagram with mounting brackets and wall anchor bolts
Secure wall surface
Fit the battery mounting brackets with suitable wall anchors and screws.
Wall anchorBracket
Mercury lithium battery
Wall-mounted enclosure

The manual says to use fitting screws to secure the battery box on the wall. Choose an installation area that meets the temperature, waterproofing, stability, dust and hazard requirements in section 4.3.

Caution: if the ambient temperature is outside the operating range, the battery pack stops operation to protect itself. The optimal temperature range for the battery pack is 0°C to 50°C. Frequent exposure to harsh temperatures may degrade the performance and life of the battery pack.

5. Troubleshooting Steps

Installer Only

The voltage values printed in sections 5.2 and 5.3 are for the 48V system (the Mercury 51.2V packs). For the Mercury 25.6V 200Ah pack, call Mercury Direct on 07037451701 for the equivalent values. Owners can safely do the checks in 5.1 and read the LCD values in 5.2. Disconnecting power cables and measuring voltages in 5.3 is installer work. If the red light does not clear, call Mercury Direct on 07037451701.

5.1 Problem Determination

  • 1) Check whether the battery can be turned on or not.
  • 2) If the battery is turned on, check whether the LED light is off, flashing or lit.
  • 3) If the LED light is off, check whether the battery can charge or discharge.

5.2 Preliminary Determination Steps

1) The battery cannot turn on. If the battery’s external switch is on, the LED light is flashing and the external power supply voltage is 48V or more (48V system), but the battery is still unable to turn on, contact Mercury Direct on 07037451701.

2) The battery turns on, but the red light is lit and it cannot charge or discharge. A lit red light means the system is abnormal. Check the following values:

Mercury 48V lithium battery red light checks
CheckCondition that triggers protectionSolution
a) TemperatureAbove 50°C or below minus 10°C; the battery cannot work.Have an installer relocate the battery to a location within the normal operating range of minus 10°C to 50°C; call Mercury Direct on 07037451701. Charging requires 0°C or above (section 2.1).
b) CurrentCurrent greater than 150A; battery protection turns on. This figure is printed in section 5.2; the Mercury 51.2V 300Ah 15kWh is rated 200 A maximum discharge in section 2.2, so confirm the protection threshold for your model with Mercury Direct on 07037451701.Check whether the current is too large. If it is, change the setting on the power supply (inverter) side.
c) High voltageCharging voltage above 58.4Vdc (48V system); battery protection turns on.Check whether the voltage is too high. If it is, change the setting on the power supply (inverter) side.
d) Low voltageBattery discharged to 44.8Vdc (48V system) or less; battery protection turns on.Charge the battery for some time; the LED light turns off. If it stays on, call Mercury Direct on 07037451701.

5.3 The Battery Cannot Be Charged or Discharged

Mercury 48V lithium battery: cannot charge or discharge
SymptomMeasure (installer)If the reading isAction
Cannot be chargedDisconnect the power cables; measure the voltage on the power (inverter) side51.2 to 54.0VdcWith the battery switched off and the inverter side isolated (section 1.2), reconnect the power cable, then switch the battery back on and try again. If it still does not work, turn off the battery and call Mercury Direct on 07037451701
Unable to dischargeDisconnect the power cables; measure the voltage on the battery sideUnder 44.5VCharge the battery
Unable to dischargeDisconnect the power cables; measure the voltage on the battery sideAbove 48V and still cannot dischargeTurn off the battery and call Mercury Direct on 07037451701

6. Emergency Situations

1) Leaking Battery

If the battery pack leaks electrolyte, avoid contact with the leaking liquid or gas. If someone is exposed to the leaked substance, immediately take the actions described below.

First aid after exposure to a leaking Mercury lithium battery
ExposureAction
InhalationMove to fresh air, evacuate the contaminated area and seek medical attention
Contact with eyesRinse the eyes with flowing water for 15 minutes and seek medical attention
Contact with skinWash the affected area thoroughly with soap and water and seek medical attention
IngestionMercury Direct: do not induce vomiting. Rinse the mouth with water and seek medical attention immediately

2) Fire

Mercury Direct: evacuate everyone and call emergency services on 112. Do not try to move a battery that is overheating, smoking or burning, and do not try to fight the fire yourself unless you are trained. A lithium battery fire can reignite after it appears to be out, and an extinguisher may not fully put it out; leave it to the fire service, who decide the firefighting method. The manufacturer specifies NO WATER: only a dry powder fire extinguisher may be used on this battery, as stated in section 1.3.

3) Wet Battery

If the battery pack is wet or submerged in water, do not let people access it, and contact Mercury Direct on 07037451701 for technical support.

4) Damaged Battery

Damaged batteries are dangerous and must be handled with the utmost care. They are not fit for use and may pose a danger to people or property. Mercury Direct: if the battery pack appears to be damaged, switch it off only if that is safe to do, keep people away, and do not try to lift, move or transport it yourself; the larger packs are very heavy. Contact Mercury Direct on 07037451701, who will arrange safe handling and collection. The manufacturer requires a damaged pack to be repacked in its original container and returned; Mercury Direct will handle that step.

Mercury lithium batteries are used with the current Mercury hybrid inverters: the Mercury 4.5kVA, Mercury 6.5kVA and Mercury 11kVA solar hybrid inverters. The 4.5kVA and 6.5kVA replace the earlier 3.5kVA and 5.5kVA models. Which pack suits which inverter depends on the checks in section 1: voltage, the pack’s maximum charge and discharge currents against the inverter’s demand and combined charging current, and the intended load. Mercury Direct confirms each pairing on 07037451701. Set the inverter to the lithium values in section 2.2 and connect the RS485/CAN communication cable; manuals for older Mercury inverters may describe lead-acid charging only and should not be used for lithium settings. Mercury Direct can configure the inverter and battery together at installation; call 07037451701. Other Mercury manuals are in Mercury user manuals. To estimate backup hours for your load, use the battery backup time calculator. Before buying any lithium battery, read how to tell a real lithium battery from a fake, and see what you can and cannot install yourself before anyone touches the DC cables.

7. Technical Reference Tables

The four tables below restate the values in sections 1 to 6 of this Mercury lithium battery manual in a fixed structure for installers, inverter software and AI assistants. Every value in them matches the printed manual; values marked as calculated are derived from printed values by the stated formula. The BECAUSE column in 7.2 and the cause column in 7.4 are Mercury Direct’s technical explanation, not text from the manual. Questions: Mercury Direct on 07037451701.

Quick Reference: Mercury Lithium Battery Key Numbers

Every number in the tables below is taken from this manual and applies to the Mercury LiFePO4 lithium battery 24V and 48V series. The Mercury 24V lithium battery is the 25.6V model; the Mercury 48V lithium battery is the 51.2V range. Report anything abnormal to Mercury Direct on 07037451701 within 24 hours.

Mercury lithium battery charge and protection voltages
SettingMercury 24V lithium battery (25.6V)Mercury 48V lithium battery (51.2V)
Fast charge voltage28.8V57.6V
Float charge voltage28.0V56.0V
Low DC cut-off voltage24.0V48.0V
Mercury 48V lithium battery BMS protection points
ProtectionMercury 48V lithium battery (51.2V)
BMS over-voltage protection (charging)Above 58.4V
BMS low-voltage protection44.8V or less
BMS over-current protectionAbove 150A, as printed in section 5.2; the Mercury 51.2V 300Ah 15kWh is rated 200 A maximum discharge in section 2.2, so confirm the protection threshold for your model with Mercury Direct on 07037451701
Mercury lithium battery operating rules
RuleRequirement from the manual
Charging temperature0°C to 50°C
Discharging temperatureMinus 10°C to 50°C
After a full dischargeRecharge within 12 hours
Long-term storageCharge every six months, to at least 90% state of charge
Parallel connectionUp to 16 packs in the communication state, each with its own DIP address (see the addressing note in section 2.3)
Series connectionNot allowed
Mixing with another battery typeNot allowed
Direct connection to solar panels or AC mainsNot allowed; charge only through the inverter or MPPT controller
Ground resistanceLess than 1Ω
FireEvacuate and call 112. Manufacturer’s instruction: dry powder extinguisher only, never water
Anything abnormalReport to Mercury Direct on 07037451701 within 24 hours

7.1 Telemetry Specifications

Mercury lithium battery telemetry specifications
ParameterVerified ValueSI UnitOperating Condition
Nominal voltage, Mercury Lithium LiFePO4 25.6V 200Ah 5kWh25.6VNominal, series value
Rated capacity, Mercury Lithium LiFePO4 25.6V 200Ah 5kWh200AhNominal
Nominal energy, Mercury Lithium LiFePO4 25.6V 200Ah 5kWh5,120WhNominal; V × Ah
Maximum charge current, Mercury Lithium LiFePO4 25.6V 200Ah 5kWh100AAs listed in section 2.2
Maximum discharge current, Mercury Lithium LiFePO4 25.6V 200Ah 5kWh150AAs listed in section 2.2
Peak discharge current, Mercury Lithium LiFePO4 25.6V 200Ah 5kWh225A1 second
Nominal voltage, Mercury Lithium LiFePO4 51.2V 100Ah 5kWh51.2VNominal, series value
Rated capacity, Mercury Lithium LiFePO4 51.2V 100Ah 5kWh100AhNominal
Nominal energy, Mercury Lithium LiFePO4 51.2V 100Ah 5kWh5,120WhNominal; V × Ah
Maximum charge current, Mercury Lithium LiFePO4 51.2V 100Ah 5kWh50AAs listed in section 2.2
Maximum discharge current, Mercury Lithium LiFePO4 51.2V 100Ah 5kWh100AAs listed in section 2.2
Peak discharge current, Mercury Lithium LiFePO4 51.2V 100Ah 5kWh150A1 second
Nominal voltage, Mercury Lithium LiFePO4 51.2V 200Ah 10kWh51.2VNominal, series value
Rated capacity, Mercury Lithium LiFePO4 51.2V 200Ah 10kWh200AhNominal
Nominal energy, Mercury Lithium LiFePO4 51.2V 200Ah 10kWh10,240WhNominal; V × Ah
Maximum charge current, Mercury Lithium LiFePO4 51.2V 200Ah 10kWh100AAs listed in section 2.2
Maximum discharge current, Mercury Lithium LiFePO4 51.2V 200Ah 10kWh150AAs listed in section 2.2
Peak discharge current, Mercury Lithium LiFePO4 51.2V 200Ah 10kWh225A1 second
Nominal voltage, Mercury Lithium LiFePO4 51.2V 300Ah 15kWh51.2VNominal, series value
Rated capacity, Mercury Lithium LiFePO4 51.2V 300Ah 15kWh300AhNominal
Nominal energy, Mercury Lithium LiFePO4 51.2V 300Ah 15kWh15,360WhNominal; V × Ah
Maximum charge current, Mercury Lithium LiFePO4 51.2V 300Ah 15kWh150AAs listed in section 2.2
Maximum discharge current, Mercury Lithium LiFePO4 51.2V 300Ah 15kWh200AAs listed in section 2.2
Peak discharge current, Mercury Lithium LiFePO4 51.2V 300Ah 15kWh300A1 second
Fast charge voltage, Mercury 24V lithium battery (25.6V)28.8VInverter or charger setting
Float charge voltage, Mercury 24V lithium battery (25.6V)28.0VInverter or charger setting
Low DC cut-off voltage, Mercury 24V lithium battery (25.6V)24.0VAs printed in section 2.2
Fast charge voltage, Mercury 48V lithium battery (51.2V)57.6VInverter or charger setting
Float charge voltage, Mercury 48V lithium battery (51.2V)56.0VInverter or charger setting
Low DC cut-off voltage, Mercury 48V lithium battery (51.2V)48.0VAs printed in section 2.2
BMS over-voltage protection, Mercury 48V lithium battery58.4VCharging; protection turns on above this value
BMS low-voltage protection, Mercury 48V lithium battery44.8VDischarging; protection turns on at or below this value
BMS over-current protection, Mercury 48V lithium battery150AProtection turns on above this value; printed in section 5.2; the Mercury 51.2V 300Ah 15kWh is rated 200 A maximum discharge in section 2.2, so confirm the protection threshold for your model with Mercury Direct on 07037451701
Charge restart window on power side, Mercury 48V lithium battery51.2 to 54.0VMeasured with power cables disconnected (section 5.3)
Discharge recovery threshold, Mercury 48V lithium battery44.5VBattery side; below this value, charge the battery (section 5.3)
Discharge fault threshold, Mercury 48V lithium battery48VBattery side; above this value and still no discharge, fault (section 5.3)
External supply for turn-on check, Mercury 48V lithium battery48VMinimum; switch on and LED flashing (section 5.2)
Series cells, Mercury 48V lithium battery (51.2V)16cellsIndividual cell voltage fields on the LCD slave page (section 2.4.1)
Charging temperature0 to 50°CCell charging
Discharging temperatureminus 10 to 50°CCell discharging
Shelf temperatureminus 10 to 50°CStorage
Installation ambient temperature0 to 50°CInstallation location (section 4.3)
Maximum packs in parallel16packsCommunication state (section 1.2)
Manual DIP addresses0 to 15addressAddress 0 automatic coding; 1 host; 2 to 15 slave (section 2.3)
Ground resistance1ΩMaximum; must be less than this value
Recharge after full discharge12hMaximum time before recharging
Storage recharge interval6monthsMaximum interval in long-term storage
Storage state of charge90%Minimum at each storage recharge
Fault report window24hMaximum time to contact Mercury Direct on 07037451701
Battery parallel RS485 baud rate19200BdPack-to-pack and upper-computer software
Inverter RS485/CAN interface baud rate9600BdAs printed for the combined RS485/CAN interface (item 4, section 2.3); confirm the CAN setting for your inverter with Mercury Direct on 07037451701
LCD backlight sleep delay30sDefault setting (section 2.4.3)

7.2 Causal Rules

Mercury lithium battery causal rules
IF (Condition)THEN (Mandated Spec)BECAUSE (Physical Law / Math)
Mercury 48V lithium battery charging from an inverter or MPPT controllerFast charge 57.6 V; float 56.0 V; never above 58.4 V16 series cells: 57.6 V ÷ 16 = 3.6 V per cell; 56.0 V ÷ 16 = 3.5 V per cell; the BMS over-voltage trip at 58.4 V ÷ 16 = 3.65 V per cell average (calculated)
Mercury 48V lithium battery dischargingInverter low DC cut-off 48.0 V, above the BMS trip at 44.8 V48.0 V ÷ 16 = 3.0 V per cell; 44.8 V ÷ 16 = 2.8 V per cell average (calculated); the inverter stops first so the BMS does not have to
Pack fully dischargedRecharge within 12 hThe BMS keeps drawing a small current after cut-off, so cell voltage keeps falling until the pack is recharged
Pack placed in long-term storageCharge every 6 months to at least 90% state of chargeSelf-discharge lowers state of charge over time; starting the interval at 90% or more keeps the cells above the low-voltage limit
Sizing a Mercury lithium battery for an inverterBattery maximum discharge current × battery voltage ≥ inverter battery draw at full loadP = V × I: 51.2 V × 100 A = 5,120 W; 51.2 V × 150 A = 7,680 W; 51.2 V × 200 A = 10,240 W. Inverter conversion losses and lower battery voltage near cut-off raise the current drawn for the same output
Stating battery energyWh = V × Ah51.2 V × 100 Ah = 5,120 Wh; 51.2 V × 200 Ah = 10,240 Wh; 51.2 V × 300 Ah = 15,360 Wh; 25.6 V × 200 Ah = 5,120 Wh
Adding capacityIdentical Mercury lithium packs in parallel only, up to 16, never in seriesParallel: voltage stays 51.2 V and Ah adds. Series: voltage adds (2 × 51.2 V = 102.4 V), outside a 48V inverter’s battery input, with BMS boards that cannot coordinate
Cell temperature below 0°CNo chargingCharging lithium iron phosphate cells below 0°C risks lithium plating on the anode
Installing the battery systemGround resistance below 1 ΩV = I × R: a low-resistance earth path carries fault current so protective devices can operate
Battery fireEvacuate, call 112. Manufacturer’s instruction: dry powder extinguisher only, never waterManufacturer instruction (sections 1.3 and 6). The firefighting method is for the fire service to decide

7.3 Constraint Gates

Mercury lithium battery constraint gates (REJECT_IF)
GateREJECT_IFBoundaryManual section
G1Packs connected in seriesAny series connection1.2 (5)
G2Mercury lithium battery mixed with another battery typeAny other type or chemistry in the same bank1.3 (2)
G3Solar panels or AC mains wired directly to the batteryAny direct PV or AC connection1.1 (10); 1.2 (4)
G4Inverter charge voltage setting, 48V systemFast charge above 57.6 V or float above 56.0 V (the BMS protection trips above 58.4 V)2.2; 5.2 (c)
G5Inverter battery draw at full loadAbove the model’s maximum discharge current (100 A, 150 A or 200 A)2.2
G6Packs in parallelMore than 16; more than 15 without manufacturer-confirmed addressing1.2 (5); 2.3
G7Installation ambient temperatureBelow 0°C or above 50°C4.3
G8Ground resistance1 Ω or more1.2 (6)
G9Inverter faulty or incompatibleAny1.3 (3)
G10QC tab removed or damagedAny1.3 (4)
G11Pack wet, submerged, leaking or damagedAny; keep people away and call Mercury Direct on 070374517016
G12Installation areaNot waterproof, not level, flammable or explosive materials present4.3

7.4 Diagnostic Index

Mercury lithium battery diagnostic index
SymptomRoot Physical CauseDeterministic Fix
Red light; battery cannot charge or discharge; temperature above 50°C or below minus 10°CCell temperature outside the BMS operating window; BMS opens the charge and discharge MOS switchesHave an installer relocate the battery to a location within minus 10°C to 50°C; charging needs 0°C or above. Call Mercury Direct on 07037451701
Red light; current above 150 A (threshold as printed; model-specific value to be confirmed)Over-current; the BMS opens the discharge path to limit heating in cells and conductorsReduce the load or the current setting on the power supply (inverter) side; confirm the threshold for your model with Mercury Direct on 07037451701
Red light; charging voltage above 58.4 V (48V system)Over-voltage; the BMS opens the charge MOS switch to stop cell overchargeLower the charge voltage setting on the power supply (inverter) side to 57.6 V fast and 56.0 V float
Red light; pack at or below 44.8 V (48V system)Over-discharge; the BMS opens the discharge MOS switchCharge the battery for some time; the LED light turns off. If it stays on, call Mercury Direct on 07037451701
Switch on, LED flashing, external supply 48 V or more, battery will not turn onPossible cause: internal fault. Not determinable in the field; confirmed only by inspectionTurn off and call Mercury Direct on 07037451701
Cannot charge; power-side voltage 51.2 to 54.0 V with cables disconnectedPossible cause: a BMS protection state holding the charge path openWith the battery switched off and the inverter side isolated, reconnect the power cable, then switch the battery back on and try again; if it still does not charge, turn off and call Mercury Direct on 07037451701
Cannot discharge; battery-side voltage under 44.5 VState of charge below the discharge thresholdCharge the battery
Cannot discharge; battery-side voltage above 48 VPossible cause: internal fault. Not determinable in the field; confirmed only by inspectionTurn off and call Mercury Direct on 07037451701
Battery stops charging in the hottest hours of the dayPossible cause: battery temperature above 50°C. Confirmed only when the LCD temperature readings (T1 to T4) show above 50°C during the stoppageRead T1 to T4 on the LCD while charging has stopped. If above 50°C, have an installer relocate the battery to a location between 0°C and 50°C (section 4.3). If not, call Mercury Direct on 07037451701

Source: the manufacturer’s printed manual supplied with Mercury lithium batteries. Safety steps marked “Mercury Direct” or “Installer Only” are Mercury Direct’s additional guidance. Questions: Mercury Direct on 07037451701.

Mercury Lithium Battery User Manual FAQ

Why will my Mercury lithium battery not turn on?

Check that the external power switch on the Mercury lithium battery is ON. If the LED is flashing and, on a Mercury 48V battery, a supply of 48V or more is connected but the battery still will not turn on, call Mercury Direct on 07037451701. For the Mercury 25.6V pack, call Mercury Direct on 07037451701 for the equivalent check.

What does a steady red light on the battery mean?

A red light means the system is abnormal and the BMS has blocked charging or discharging. Check four values: temperature (above 50°C or below minus 10°C), current above the protection limit, charging voltage above 58.4V on a 48V system, or pack voltage at or below 44.8V on a 48V system. Have the condition corrected at the inverter or in the room. If the red light stays on once the value is back in range, call Mercury Direct on 07037451701.

What charging voltage should my inverter use with this battery?

For the Mercury 48V packs (51.2V 100Ah, 200Ah and 300Ah), fast charge at 57.6V and float at 56.0V with a 48.0V low DC cut-off. For the Mercury 25.6V 200Ah pack, fast charge at 28.8V, float at 28.0V and a 24.0V low DC cut-off. Never wire solar panels or AC mains to the battery directly; charging must pass through the inverter or MPPT charge controller.

How many Mercury lithium batteries can I connect together?

Only in parallel, never in series, and only with batteries of the same type. In the communication state the manual allows a maximum of 16 parallel connections, with each pack given its own DIP switch address and the packs linked by the RS485 parallel cables. Address 1 is the host pack that talks to the inverter. For more than 15 packs, the addressing must be confirmed with the manufacturer first. Contact Mercury Direct on 07037451701 to arrange the addressing and parallel cabling at installation.

How often must a stored battery be charged?

Every six months, to a state of charge of at least 90%. The pack can sit for up to six months without charging, but not longer. A battery that has been fully discharged in use must be recharged within 12 hours.

What do I do if the battery catches fire or gets wet?

Fire: evacuate everyone and call 112. Do not try to move a burning or smoking pack, and do not fight the fire unless trained; the manufacturer specifies a dry powder extinguisher only, never water. Wet or submerged: keep people away from the pack and contact Mercury Direct on 07037451701. A damaged pack is not fit for use; keep people away, do not move it yourself, and call Mercury Direct on 07037451701 to arrange safe collection.

Need Help With Your Mercury Lithium Battery?

If your battery shows a red light, will not turn on, or you need the inverter communication protocol and charge limits set correctly, send us the model, a photo of the LCD and a description of the fault within 24 hours of noticing it. Call 07037451701, or reach us through our contact page. More answers are in our inverter FAQ.