Mercury Solar Hybrid Inverter 3.5KVA and 5.5KVA User Manual

Mercury Solar Hybrid Inverter 3.5KVA and 5.5KVA User Manual

1 ABOUT THIS MANUAL

1.1 Purpose

This manual describes the assembly, installation. operation and troubleshooting of Mercury Solar Hybrid Inverters 3.5KVA and 5.5KVA. Please read this manual carefully before installations and operations. Keep this manual for future reference.

1.2 Scope

The Mercury Solar Hybrid Inverter 3.5KVA and 5.5KVA User Manual provides safety and installation guidelines as well as information on tools and wiring.

2 SAFETY INSTRUCTIONS

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.

2. CAUTION –To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.

3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.

4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.

5.. CAUTION – Only qualified personnel can install this device.

6. NEVER charge a frozen battery.

7. For optimum operation of this inverter/charger, please follow the required spec to select appropriate cable size. It’s very important to correctly operate this inverter/charger.

8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.

9. Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for the details.

10. One piece of 150A fuse is provided as overcurrent protection for the battery supply.

11. GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.

12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.

13. Warning! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to the local dealer or service center for maintenance.

3 INTRODUCTION

This is a multi-function inverter/charger, combining functions of inverter, solar charger and battery charger to offer uninterruptible power support. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.

3.1 Features

  • Pure sine wave inverter.
  • Configurable input voltage range for home appliances and personal computers via LCD setting.
  • Configurable battery charging current based on applications via LCD setting.
  • Configurable AC/Solar Charger priority via LCD setting.
  • Compatible to mains voltage or generator power.
  • Auto restart while AC is recovering.
  • Overload/ Over temperature/ short circuit protection.
  • Smart battery charger design for optimized battery performance.
  • Cold start function.

3.2 Basic System Architecture

The following illustration shows basic application for this inverter/charger. It also includes following devices to have a complete running system:

  • Generator or Utility.
  • PV modules.

Consult with your system integrator for other possible system architectures depending on your requirements.

This inverter can power all kinds of appliances in home or office environments, including motor-type appliances such as tube light, fan, refrigerator and air conditioner.

Mercury Solar Hybrid Inverter Basic System Architecture

3.3 Product Overview

Mercury Solar Hybrid Inverter 3.5kva and 5kva Product Overview

  1. LCD display 
  2. Status indicator 
  3. Charging indicator 
  4. Fault indicator 
  5. Function buttons 
  6. Power on/off/bypass switch
  7. AC input 
  8. AC output 
  9. PV input 
  10. Battery input
  11. Circuit breaker 
  12. USB communication port
  13. RS-232 communication port 

4 INSTALLATION

4.1 Unpacking and Inspection

Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package:

  1. The unit x 1
  2. User manual x 1
  3. DC Fuse x 1
  4. Ring terminal x 1
  5. Strain relief plate x 1
  6. PV wire cover x 1
  7. Screws x 4

4.2 Preparation

Before connecting all wirings, please take off bottom cover by removing two screws as shown below.

Mercury Solar Hybrid Inverter 3.5kva and 5kva Wirings

4.3 Mounting the Unit

Consider the following points before selecting where to install:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface
  • Install this inverter at eye level in order to allow the LCD display to be read at all times.
  • For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
  • The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.
  • Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.

SUITABLE FOR MOUNTING ON CONCRETE OR 0THER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing two screws. It’s recommended to use M4 or M5 screws.

Install Mercury Solar Hybrid Inverter screwing two screws

4.4 Battery Connection

CAUTION: For safety operation and regulation compliance it’s requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it’s still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It’s very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable as below.

Recommended battery cable size:

Model Wire Size:

Mercury Solar Hybrid Inverter wire size

Please follow below steps to implement battery connection:

1. Remove insulation sleeve 18 mm for positive and negative conductors.

2. Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.

3. Fix strain relief plate to the inverter by supplied screws as shown in below chart.

Fix Mercury Solar Hybrid Inverter strain relief plate

4. Connect all battery packs as below chart.

Mercury Hybrid Inverter Battery Connection

5. Insert the battery wires flatly into battery connectors or inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals.

Recommended tool: #2 Pozi Screwdriver

Mercury Solar Hybrid Inverter 3.5kva and 5kva battery terminals

6. To firmly secure wire connection, you may fix the wires to strain relief with cable tie.

Mercury Solar Hybrid Inverter 3.5kva and 5kva Installation with care high battery voltage in series

WARNING: Shock Hazard

Installation must be performed with care due to high battery voltage in series.

CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).

4.5 AC Input/Output Connection

CAUTION!! Before connecting to the AC input power source, please install a separate AC breaker between the inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec for 3.5KW and 50A for 5.5KW.

CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by qualified personnel.

WARNING! It’s very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested cable requirement for AC wires

17HC0QcxgvQxpgpTtrBXaytKQr61yibCc0P8yG pFNcXrakZEibc tzWSoC806UhSX8zQXSzQebWOe ChsMjcxdd 5gW7BYlj5kqLh7XxSNGDRJUMViDL4hKZjyIKs

Please follow below steps to implement AC input/output connection:

1. Before making an AC input/output connection, be sure to open the DC protector or disconnector first.

2. Remove the insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.

3. Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor first.

Ground (yellow-green)

L-LINE (brown or black)

N-Neutral (blue)

Ywf4xMAWGn2N902lSersByxwdZGgFxMSCxLwj zwiFCowEvTRHq22E0rmljxRCjZDW99t3Us2VL8atlTXkziqf MFjTHasXL2MweEvD7cJdzFdIdAmNlgTmK8uecjZ XNWa82hWipz8Qd4AaDYBYk3MvpT2Ur9FuU1I7omLYFbf1md1khE1IUdrbsegnSQ

WARNING:

Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.

4. Then, insert AC output wires according to polarities indicated on the terminal block and tighten terminal screws. Be sure to connect the PE protective conductor first.

Ground (yellow-green)

L-LINE (brown or black)

N-Neutral (blue)

g3dVlvVEPeooWcUi4mo28vzW5WNv4GXmlntoBsb3XM1 rJAGtT8g8cwl3LK1HPsB0kPi82LW7nxS3HjSCHmeUqWKJKCPMrQZufS6 QqOMoCizFuJdCirSW C1SCz3QtoT6qiOoeQkiRaqaM5sgnHRsLrcJ1JrRMsXvsmKsxRMuUZTsbVKlCOp 1saa6TuQ

5. Make sure the wires are securely connected.

CAUTION: Appliances such as air conditioner are required at least 2-3 minutes to restart because it’s required

to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check the manufacturer of the air conditioner if it’s equipped with a time-delay function before installation. Otherwise, this

inverter/charger will trigger overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.

4.6 PV Connection

CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter

and PV modules.

WARNING! It’s very important for system safety and efficient operation to use appropriate cable for PV

module connection. To reduce risk of injury, please use the proper recommended cable size as below.

LsN3TXhgx fuRwWbCFaW4QDrcMdBsABVkvt kF4ro7tHN323VKEuXDp4SUd y LsP4AAWWR8k8dVeV67SjueRZZNUizN0UZfBEkBv gZrvBJLf93McNB6V3eJCKb3fbg4EDfMTCYqNUok9iyIjwaaBeb1

PV Module Selection:

When selecting proper PV modules, please be sure to consider below parameters:

1. Open circuit Voltage (Voc) of PV modules does not exceed max. PV array open circuit voltage of inverter.

2. Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.

5q5B305CEYH4e KrE CSPQYHATqds2M9fOAP6NLHaD6OnEG4wWVq EnxyiA2ACtHJSAbFzy SHi2C5BnuuI3 W4pnA3c7 bkR36iKclzsqe

Take the 250Wp PV module as an example. After considering the above two parameters, the recommended module configurations are listed as below table.

U1PlvFuEzI ve6FlniM Yhc 54zpFxNqlIWgU2qy8 A0Kdo HCPb dY4i9vdnPKtGMBpInkEBVRqeVvQmWSCX4ylWZRHnIyrxpsG54VhwLWQcKaO0W45fByFNbo FQz6Cbc46 uXvMhwgM97DtbFbkSS2fJxq75rXvVc 2m0aEgVw3nEJfFzTq dySGyw

PV Module Wire Connection

Please follow below steps to implement PV module connection:

1. Remove the insulation sleeve 10 mm for positive and negative conductors.

2. Suggest to put bootlace ferrules on the end of positive and negative wires with a

proper crimping tool.

3. Flx PV wire cover to the inverter with supplied screws as shown in below chart.

g8BSU49NJ2x4 seQg1MN50ekXmyAlTLVKeLT6ztKR2aQzlt 4V8eAkaLAIIQhySZWJWMFHKz3ZgdX1A9s7xL30IBLaR 6Aw5us Rvnm1pC5OtYsMFjVUbg8hSaC40hcevNLZgW

4. Check correct polarity of wire connection from PV modules and PV input connectors. Then, connect positive

pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector. Screw two wires tightly in clockwise direction. Recommended tool: 4mm blade screwdriver

rMm4sj dn6PEWxOrKiCDgIr9kJcmJaTvqE3Z4imFEYAdQZIUBQVT5ZEmUS3ugSbBra p ZnPvu55lRbkGxY3uajlFUXa8h7mP1VOq9P5pWVRNi5yLN8QtDXP72VBzOcEvjQKBfE1YCD7yv8ep55CoEBQB4TPvQQPYGjU5d7sTF

4.7 Final Assembly

After connecting all wirings, please put the bottom cover back by screwing two screws as shown below.

ZzdBku5jyp TWEpdKjiEreLZelPEykbZlIkNojc3gn1 EgAMNWnTb1ve3TUEj6SaSUp8Ug r dyeiMG88yPJMcI1brhRlJvs

4.8 Communication Connection

Wi-Fi cloud communication (option):

Please use the supplied communication cable to connect to the inverter and Wi-Fi module. Download APP and install it from the APP store, and Refer to “Wi-Fi Plug Quick Installation Guideline” to set up the network and register. The inverter status would be shown by mobile phone APP or webpage of computer.

GPRS cloud communication (option):

Please use the supplied communication cable to connect to the inverter and GPRS module, and then apply external power to the GPRS module. Download APP and install it from the APP store, and Refer to “GPRS RTU Quick Installation Guideline” to set up the network and register. The inverter status would be shown by mobile phone APP or webpage of computer.

5 OPERATION

5.1 Turn ON/OFF/BYPASS

Slide view of unit 

hXxPhf7K qaGrjV8YUhoc4 jCR9AKtZkF8woXpM2NAuWF18QU 9cXdxzrAL77aP zyem5c0zdpagyvZcLAWuwATLQxZcPpJdMbU6TlRUiIlF6OuhbVbXJGiQvxIKHvEKl

Once the unit has been properly installed and the batteries are connected well, simply turn On/Off/Bypass switch (located on the side of the case) to turn on the unit

5.2 Operation and Display Panel

The operation and display panel, shown in below chart, is on the front panel of the inverter. It includes three indicators, four function keys and a LCD display, indicating the operating status and input/output power information.

2wd4dYKLvWSHLq DwcvMeh50ZmyjLw3CGDGr 4cyZJeIPtybpBT3Heyk5vpI6G4MhG8 VoUoVDYJTeX3d2zEG14gc1MWASFGQ2sLxewB UAuq CdFsCe33OpptG7dG7KWonoEopIUhX4 PAcoB IWxd xIJQ2 7HcUPJyd4NnzmEM PFD9V2yInWrE nkw

5.3 LCD Display Icons 

MSlY2TJx7WQGpI C56GLCaDNPJ9kQ54lGueH6VWVdAKX7PzUTM9PXeEwonvvG6fB4VNBPqZhORceM0wUeFng5Yj97E4lo52I 18zvs HUJhy l 7N NLNfaDrV vYPlzRdo6nkB2 05HTyTU oI96QIidvdZ 4HXENoGNTr25zMtrmV2zZgBH13Kbwuw
IlLxeBcfzVi TsZfkMCB hWl0M6uT7vho cpNbnJ9n3Z8 TzxqnFJJrlgbcL5ZC 02REE8tI8sOiwrr3XID31UR4IqWIsdLj9trRBnr1TtvUtoGcbT4aV0QMb5GbW45jLcb3LSzC7hwcXKKAFk2hukjQaUSRXXbvssHWX9ArSWCUjTTvRbQzCdt5544Uqw
j e658eR0vFPIFNs7yPcwNNmExU3CwFnLZ2Rx109pLq2iAcOeKY 3qVsyaz8HfiUBJjg1QE5XD8DNq SbeJ7fqf6puIBG1 VLtZhfvR2UbNBue5eHacuAcwj2hyYFd7iaHFtfcjg7ETpHl6HENHedeM2ZOgr4f1bhvLaBz3k9MCWkbGiLO06vkjFg1wr3w

5.4 LCD Setting

After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press “UP” or “DOWN” button to select setting programs. And then, press the “ENTER” button to confirm the selection or ESC button to ext.

Setting programs:

rImN3 J0fWIiHmTeipwT5qmJ9COYpw3I43TaG TYu5DeNQ7galKGLVK ZRtPahxwtYD3YZ33WEVKyY3Fz uHxOCMxyj3J8 CaYun5SaOaVnZUSjR3a
xSi0a320 w9VLsND5UT5GxoaIlfVoNRxvyLzeAHMDZIW57GY RD8 Molq5UJyEEMWOlfw sy73syxI fx9EL2ID6J0fJIoY1kBpzrM0Uk2DnMBZuQbNIWywms9JS2PzkghdmiSKieT6JnUZfbDLDkT vCpht6e0VYTD6JtLw obkqXoQM NHjyQvFoYVTg
DR8AQpnuTTQ16ll8g 7Rv2i3NdbMTPKTS b 9cpIi9hUbSr4N9ryTFWnNG O45w JwUj s05rWKBhdgVCunX8sGARlAKf6dmqa684RvlRt WjcjSa3UXAKbh9KErkGqkNHMRAtbZLgFLOW6KeBsFKL5g9 YKHae nBZ38S tzhHYFTdYTW6ATJrvBmJAmw
FZ 1FdMfj wvzdNobZrKYwRADaWnojtgGiHRHiFa 59LLBRIGLqxjo0yNZxbiagVzG K8XOS4MPLILGV1oQ1nO4Ezt5GdqZKL0G FbyvMY6SeCuBPjNVR6Nd1MhkFIOHhUjuis393thfO4cKN18Q58FYaG0UZIQbPeNpGtVTaAvHN07OWZnry5VMbnoccA
ny9Aol ciMsX5ZFJAwuoEaehlpO3BECtI2tqka BrJQjkQjx10z oIqyBzd4lSI28K sbqj5RpZ6OmQ xEvXvlnlo7R2FDLROzg9TOyOferCGZ4jUdsSck7r 6jtTdgBkiA9earOy19248HRwP3GqKgBM3uU9exqsewH kmNORlDKbrucH1DuCYZOcRH8g
ME8NgpCoG AsDVPmnTPlUEom9G7IFIqqHeGIG1yftA2wrA dYHswF ogZuNeqsOt11JxaFlEm4w42yQLiZ Sw206CWPQVHlB79VqGIOHXQ1 6L0BWoZ7AVuicC3jKNR76e0epApwbnz6h aLVWMYUuOwtOP6r ld1DgzGbsAbE2nKEnD1ouostrme XOtw
kk0RTdAjdi7 Ms3Gmhwm2m8ZBthvv28gBPaop8ItxmFUBI09Qr2qkj0b4HLi3M9W0fG5NOgSQGZ6DJqOBKIoB0y 8lNsJrQV7f47gIB3C9PHmz65hr Unr3xx1cOCBYULGC9SSQvrkwwTMlTOsNtYkkOWsE3tl Dq7XpdEe4uY4 i9yv g WAvrzO yOUA

5.5 Display Setting

The LCD display information will be switched in turns by pressing the “UP” or “DOWN” key. The selectable information is switched as below order: input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in Watt, DC discharging current, main CPU Version.

m3JL9QfSW6fxARJIWQwtKkyXdij1Qcz1J2ctOKJeQpclFRXEO ZHNuzhSHSy5VziwulHboOSBT3pQ21CHNYqRBPze9nHGxUD1 B0QSXOTaA7RxBvvCZB99mCNIYlA7FiAIbKepzCn5NN1j BtM4NqkD5hooYrocsn2KFP5fKZzjznRCDtMg tKMetNkOlg
OgFH0LMXtIhRac5 qdeFtdVwElOcrtmKtyfeqCDh6q6ZD5xlnwiXbIfQwM mO5WemqhxtqyEGklK809qO 4imXefPr1
UYBh8DZXXxbVVT2vV941m9kZXCvZoirspCJG2cKswr6PilRQWihW60FNGFWbk4AAu7xJR1L fkI m44U5DwpI INjWaD3v7eDyB COPpMh9qgZuycdPIo1htsKI5PjTBwuiC4oo3KIgHXu IA2LbRYBb0AcfQ22DufMyidW y9PVAA1a
2 MWRkCw puCGK15GY9JUEGZmf BdSIl8PI38fKKzz e6r2zkFCt19IG7sQlAKCHxiMzKawZTtCesUDp iz0HUKkTszs9pysGuIwthqTsnS60qbq6
SNuvSQUHzgL0nfsManBuH5a2o03Ue9QKBek4h8 ThjoMdZGhmS1WGleZomXgMxcqiczMP0V7rI5feVv5wARrISetnbM UU UHte71Q0 Dg4sJ8d kyb5 DZdtl0q0WwEkWuhQ Bd89X73Rpx4yg313 iecGXLK 3r2z591fxBejkiFc g4BogOD2oBMGQ

5.6 Operating Mode Description

7LyckvOBcecsEr326DmDIdKEvax3Sa2up8PJmPTw N5WY3i9n6eIGXe3XBYsZUAHywzqxki VTXnF1vjJaaQ8LGeiuwtCQeyQ85rIfBucLMERbvffDHRpAlsl97pIn8Uu8JKgNeoTDHBg2F1LpfBEVn6B9uhVg7CIfHcMLmVo yX98hcEUn0drawPwNDUQ
FR8snd3f1hNUpRKld7tH6Hx3oe 7aDv27 KAUjBZ9AOyvzxvfOYNolxBs1d7EdKAtLMbuiUoGgRPNar 6CuUf wgoIuu1k
bMD GMZJM6E8XgDVrANlkrLUIwB21IPpwuTBrOyS4U5d5XCZtLFgobCKlXAS7NexU5ksbuBDeO0xIQheqn u7KIxf5yEJ3woLZ8o2i RVfrW1oO3rjHD171b88OFrO2xdOKW1qLC1Ek

5.7 Battery Equalization Description

Equalization function is added into the charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it’s recommended to equalize the battery periodically.

° How to Apply Equalization Function

You must enable battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in device by either one of following methods:

1. Setting equalization interval in program 35.

2. Active equalization immediately in program 36.

° When to Equalize

In the float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter Equalize stage.

4QNHkpGdwDr6iLc0Mw wqx lTH06

° Equalize charging time and timeout

In the Equalize stage, the controller will supply power to charge the battery as much as possible until battery voltage rises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.

rVJsHxW IpVbHi4VyfpFWtdbqgh6CCCh8zaxrKJT5brXKN J5AgAate8PbcD0K1GwmKRfhTt uJSD4IoZuc0GuM lcYzRrAzElInlibqz20rlRoCZN6t ROq URJaw5IhWNVSAVxkZU34jbvpjSUnLrVXrjttR8nqysfEp5yKo5GrNlavAxXhB rOg8RgA

However, in the Equalize stage, when battery equalized time is expired and battery voltage doesn’t rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to the float stage.

TloECfVQzU8BwTfQvIMsM7 rQYBVQxdJDx5HYtuaz jUgx2f U8mVm0cFWZWEFwyAmlyiOJnskWRXuO4rgzdfIhjzE2E5ZNL44ldNb4od7Qwv8qhhCmR PsfGNv36JBu U4dlwOsOK5Bc6wEFiPqgKD94HBw7QfF JGFl6UCqi4lFa 7niBhFkM yGqAQ
TXVPET og8MreAS7JyuCkmnzM3 KHvPVpT8Vrw3OcS0lVTPouINCywAjXCrDhMwXtuInlloE2xjA1h1rCEz0qBDGPPPfxyJp1BdCU9yNe8jO5P05CK

5.9 Warning Indicator

jShLjc7P4WDofSk Qfr9 ZwAgOl3 ZgUp0jcC qHiYsenVZG QXxromJomSxp4GzryaJ CYFp MtjBr0Ff2fVtms6FjZEKx0CwKJyqTRUjA hqM d7yDiFk7DQ31DChP0e6 XOvR1U5CA4ZgmbHJuI zBcQz0sXZCWIluk qlT50Dk1fimngvlXHlVDsig

6 SPECIFICATIONS

Table 1 Line Mode Specifications

alaRh3k MIuEbZtkouffIh3R5nc3AKiJ Opqj

Table 2 Inverter Mode Specifications

1YgktWqjfDVJ mqzxYVS0PDvfWxZPJZ3bJ7tbwlSC5esNuDg6rdmVPtw6i0myc7

Table 3 Charge Mode Specifications

HpMuA2wXXcRvQF0OxOhTTiW6N5R AI27uvOoyl t82WrzQfyLeIl69ki9o2O0vHoRENnspAGIafJFUI4kuK4iOFs29tZsgeZ3iRN4 4xswqX5v1nb8IEo1R0z48AMrNEHwwuC8R

7 TROUBLESHOOTING

tkeIv4X6aErdAvXTAZQMy AbAOXaFJqJqDukHHJ4uJEAWTrTSl3TOTk CGlmehIPDhYX3o9RjMBBhd3LLeudqbRB0YTNxr8 ut8bSrsxdRCr8uvUf0WByKbAyq7OMpou9moEI8JFwdwU90nZv 41iCyXMsBteWrj SK7c3Z8IfPp LOEun3CgPE499QRQ

8 Appendix: Approximate Back-up Time Table 

JJzc93xJEWhHIokx6CZxseSiWwrVb7P7BFgMXqVq25x0wAtLXBn4I5hGCFcFCFScG1V7RLmsJPQ8Or0LF3GCJiXRnqpaJ397zqhR a0TLknmwMpLBpccmPxixOQLNMTUtf9AnaLe4PDpm4Qsshz41XmxL6q9w

Note: Back up time depends on the quality of the battery, age of battery and type of battery. 

Specifications of batteries may vary depending on different manufacturers.